Ground source heat pumps
WPF 66 – Technical Data

  • Technical data

    Heating output at B0/W35 (EN 14511)

    67,10 kW

    Heating output at B0/W55 (EN 14511)

    62.30 kW

    Power consumption at B0/W35 (EN 14511)

    14.71 kW

    Power consumption at B0/W55 (EN 14511)

    22.09 kW

    COP at B0/W35 (EN 14511)

    4.56

    COP at B0/W55 (EN 14511)

    2.82

    SCOP 35 °C (EN 14825)

    4.95

    Sound power level (EN 12102)

    59 dB(A)

    Max. application limit on the heating side

    60 °C

    Height

    1154 mm

    Width

    1242 mm

    Depth

    860 mm

    Weight

    655 kg

    Rated voltage, compressor

    400 V

    Rated voltage, emergency/auxiliary heater

    400 V

    Refrigerant

    R410A

    Technical data and product variants

    For further details and product variants please refer to data sheet.

    Download as PDF