Air source heat pumps
WPL 24 A Set – Technical Data

  • Technical data

    Energy efficiency class, heat pump W35

    A+++

    Energy efficiency class, heat pump W55

    A++

    Energy efficiency class, composite system (heat pump + controller) W35

    A+++

    Energy efficiency class, composite system (heat pump + controller) W55

    A++

    Heating output at A7/W35 (EN 14511)

    7.41 kW

    Heating output at A2/W35 (EN 14511)

    9.04 kW

    Heating output at A-7/W35 (EN 14511)

    13.45 kW

    COP at A7/W35 (EN 14511)

    4.72

    COP at A2/W35 (EN 14511)

    4.00

    COP at A-7/W35 (EN 14511)

    3.00

    SCOP (EN 14825)

    4.58

    Sound power level (EN 12102)

    59 dB(A)

    Min./max. application limits for heat source

    -20/40 °C

    Max. application limit on the heating side

    65 °C

    Height

    1434 mm

    Width

    1240 mm

    Depth

    1280 mm

    Weight

    279 kg

    Rated voltage, compressor

    400 V

    Rated voltage, emergency/auxiliary heater

    400 V

    Refrigerant

    R410A

    Technical data and product variants

    For further details and product variants please refer to data sheet.